Herewith below we have shared the requirements of Water Supply for fire fighting Installations.
Sl. No |
Type of Building/Occupancy |
Requirements for water supply | |
Underground tank in liters | Terrace tank in liters | ||
1 | Apartment building below 15m in height | Nil | Nil |
2 | Apartment buildings | ||
a) Above 15 m but not exceeding 24 m | Nil | 10000 | |
b) Exceeding 24m but not exceeding 45 m | 50000 | 20000 | |
c) Above 24 m and not exceeding 35m with shopping area upto 250 sq.m and restricting the shopping areas to the ground floor only | 50000 | 20000 | |
d) Above 24 m and not exceeding 35m with shopping area exceeding 250 sq.m | 100000 | 20000 | |
e) Above 45 m and not exceeding 60 m | 100000 | 20000 | |
f) Above 60 m in height, but not exceeding 92 m (apartment building above 92 m should not be permitted) | 150000 | 20000 | |
3 | Non-apartment buildings: | ||
a) Educational and industrial upto 15 m in height | 50000 | Nil | |
b) Storage and hazardous up to 15 m in height | 100000 | 20000 | |
c) Above 15 m in height but not exceeding 24m except for educational buildings | 150000 | 20000 | |
d) Educational building above 15 m but not exceeding 24m in height | Nil | 20000 | |
e) Educational and commercial buildings above 24 m but not exceeding 35 m | 150000 | 20000 | |
f) Educational and commercial buildings above 35 m but not exceeding 60 m | 200000 | Nil | |
g) Educational and commercial buildings above 35 m but not exceeding 92 m | 250000 | Nil |