Requirement of Water Supply for Fire Fighting Installations - CIVIL ENGINEERING OBJECTIVE

Requirement of Water Supply for Fire Fighting Installations

Herewith below we have shared the requirements of Water Supply for fire fighting Installations. 


 

Sl. No

 

Type of Building/Occupancy

Requirements for water supply
Underground tank in liters Terrace tank in liters
1 Apartment building below 15m in height Nil Nil
2 Apartment buildings
a) Above 15 m but not exceeding 24 m Nil 10000
b) Exceeding 24m but not exceeding 45 m 50000 20000
c) Above 24 m and not exceeding 35m with shopping area upto 250 sq.m and restricting the shopping areas to the ground floor only 50000 20000
d) Above 24 m and not exceeding 35m with shopping area exceeding 250 sq.m 100000 20000
e) Above 45 m and not exceeding 60 m 100000 20000
f) Above 60 m in height, but not exceeding 92 m (apartment building above 92 m should not be permitted) 150000 20000
3 Non-apartment buildings:
a) Educational and industrial upto 15 m in height 50000 Nil
b) Storage and hazardous up to 15 m in height 100000 20000
c) Above 15 m in height but not exceeding 24m except for educational buildings 150000 20000
d) Educational building above 15 m but not exceeding 24m in height Nil 20000
e) Educational and commercial buildings above 24 m but not exceeding 35 m 150000 20000
f)  Educational and commercial buildings above 35 m but not exceeding 60 m 200000 Nil
g) Educational and commercial buildings above 35 m but not exceeding 92 m 250000 Nil


Share to all